kVA to kW Calculator
Convert kilovolt-amps (kVA) to kilowatts (kW) by multiplying by the power factor: kW = kVA × PF. Generators are usually rated at PF 0.8.
REAL POWER
21.25 kW
IN WATTS
21,250 W
FORMULA
kW = kVA × PF
REACTIVE
13.17 kVAR
kVA to kW — Reference Table
| kVA | PF 0.7 | PF 0.8 | PF 0.85 | PF 0.9 | PF 1.0 |
|---|---|---|---|---|---|
| 5 kVA | 3.5 | 4 | 4.25 | 4.5 | 5 |
| 10 kVA | 7 | 8 | 8.5 | 9 | 10 |
| 15 kVA | 10.5 | 12 | 12.75 | 13.5 | 15 |
| 20 kVA | 14 | 16 | 17 | 18 | 20 |
| 25 kVA | 17.5 | 20 | 21.25 | 22.5 | 25 |
| 50 kVA | 35 | 40 | 42.5 | 45 | 50 |
| 75 kVA | 52.5 | 60 | 63.75 | 67.5 | 75 |
| 100 kVA | 70 | 80 | 85 | 90 | 100 |
| 150 kVA | 105 | 120 | 127.5 | 135 | 150 |
| 200 kVA | 140 | 160 | 170 | 180 | 200 |
💡 How to Convert kVA to kW
To convert kVA to kW, multiply the kVA by the power factor. kVA is apparent power and kW is real power, so kW = kVA × PF. For generators rated at the industry-standard power factor of 0.8, kW is 80% of kVA.
kVA to kW formula
Example: 25 kVA at PF 0.85 → 25 × 0.85 = 21.25 kW
Worked examples
- 100 kVA diesel generator (PF 0.8): 100 × 0.8 = 80 kW prime power.
- 62.5 kVA generator (PF 0.8): 62.5 × 0.8 = 50 kW, a common size for small commercial buildings.
- 500 kVA transformer feeding a load at PF 0.9: 500 × 0.9 = 450 kW of real power before the transformer is fully loaded.
kVA to kW table
| kVA | PF 0.7 | PF 0.8 | PF 0.85 | PF 0.9 | PF 1.0 |
|---|---|---|---|---|---|
| 1 | 0.7 | 0.8 | 0.85 | 0.9 | 1 |
| 5 | 3.5 | 4 | 4.25 | 4.5 | 5 |
| 10 | 7 | 8 | 8.5 | 9 | 10 |
| 15 | 10.5 | 12 | 12.75 | 13.5 | 15 |
| 20 | 14 | 16 | 17 | 18 | 20 |
| 25 | 17.5 | 20 | 21.25 | 22.5 | 25 |
| 30 | 21 | 24 | 25.5 | 27 | 30 |
| 50 | 35 | 40 | 42.5 | 45 | 50 |
| 62.5 | 43.75 | 50 | 53.12 | 56.25 | 62.5 |
| 100 | 70 | 80 | 85 | 90 | 100 |
| 125 | 87.5 | 100 | 106.25 | 112.5 | 125 |
| 250 | 175 | 200 | 212.5 | 225 | 250 |
| 500 | 350 | 400 | 425 | 450 | 500 |
Apparent, real and reactive power
AC power has three parts, often drawn as the power triangle. Apparent power (VA or kVA) is voltage × current: what the wiring, breaker and transformer actually carry. Real power (W or kW) is the part that does useful work, such as heat, light or motion. Reactive power (VAR) is the part that flows back and forth to build magnetic and electric fields in motors, transformers and capacitors. The power factor (PF) is the ratio of real to apparent power, between 0 and 1.
Typical power factors: resistive loads such as heaters and incandescent lamps run at 1.0; computer and server power supplies with power factor correction (PFC) run at about 0.95–0.99; induction motors run at roughly 0.8–0.9 at full load and lower when lightly loaded. Diesel generators are conventionally rated at a power factor of 0.8.
Common mistakes
- Assuming kVA = kW. A "10 kVA" generator is an 8 kW generator at PF 0.8. Buying on the kVA figure alone can leave you short of power.
- Using PF 1.0 for motor loads. Motors and compressors have lagging power factors, so real power is well below kVA.
Related conversions: kW to kVA · kVA to watts · kVA to amps