kVA to kW Calculator

Convert kilovolt-amps (kVA) to kilowatts (kW) by multiplying by the power factor: kW = kVA × PF. Generators are usually rated at PF 0.8.

kVA

REAL POWER

21.25 kW


IN WATTS

21,250 W

FORMULA

kW = kVA × PF

REACTIVE

13.17 kVAR

kVA to kW — Reference Table

kVAPF 0.7PF 0.8PF 0.85PF 0.9PF 1.0
5 kVA3.544.254.55
10 kVA788.5910
15 kVA10.51212.7513.515
20 kVA1416171820
25 kVA17.52021.2522.525
50 kVA354042.54550
75 kVA52.56063.7567.575
100 kVA70808590100
150 kVA105120127.5135150
200 kVA140160170180200

💡 How to Convert kVA to kW

To convert kVA to kW, multiply the kVA by the power factor. kVA is apparent power and kW is real power, so kW = kVA × PF. For generators rated at the industry-standard power factor of 0.8, kW is 80% of kVA.

kVA to kW formula

kW = kVA × PF

Example: 25 kVA at PF 0.85 → 25 × 0.85 = 21.25 kW

Worked examples

  • 100 kVA diesel generator (PF 0.8): 100 × 0.8 = 80 kW prime power.
  • 62.5 kVA generator (PF 0.8): 62.5 × 0.8 = 50 kW, a common size for small commercial buildings.
  • 500 kVA transformer feeding a load at PF 0.9: 500 × 0.9 = 450 kW of real power before the transformer is fully loaded.

kVA to kW table

kVAPF 0.7PF 0.8PF 0.85PF 0.9PF 1.0
10.70.80.850.91
53.544.254.55
10788.5910
1510.51212.7513.515
201416171820
2517.52021.2522.525
30212425.52730
50354042.54550
62.543.755053.1256.2562.5
10070808590100
12587.5100106.25112.5125
250175200212.5225250
500350400425450500

Apparent, real and reactive power

AC power has three parts, often drawn as the power triangle. Apparent power (VA or kVA) is voltage × current: what the wiring, breaker and transformer actually carry. Real power (W or kW) is the part that does useful work, such as heat, light or motion. Reactive power (VAR) is the part that flows back and forth to build magnetic and electric fields in motors, transformers and capacitors. The power factor (PF) is the ratio of real to apparent power, between 0 and 1.

W = VA × PF  ·  VA = W ÷ PF  ·  VAR = √(VA² − W²)

Typical power factors: resistive loads such as heaters and incandescent lamps run at 1.0; computer and server power supplies with power factor correction (PFC) run at about 0.95–0.99; induction motors run at roughly 0.8–0.9 at full load and lower when lightly loaded. Diesel generators are conventionally rated at a power factor of 0.8.

Common mistakes

  • Assuming kVA = kW. A "10 kVA" generator is an 8 kW generator at PF 0.8. Buying on the kVA figure alone can leave you short of power.
  • Using PF 1.0 for motor loads. Motors and compressors have lagging power factors, so real power is well below kVA.

Related conversions: kW to kVA · kVA to watts · kVA to amps

kW = kVA × power factor. A 100 kVA generator at PF 0.8 delivers 80 kW.

kVA to kW Calculator FAQ