kW to kVA Calculator

Convert kilowatts (kW) to kilovolt-amps (kVA) by dividing by the power factor: kVA = kW ÷ PF. Size generators, transformers and UPS systems correctly.

kW

APPARENT POWER

11.76 kVA


IN VA

11,765 VA

FORMULA

kVA = kW / PF

REACTIVE (kVAR)

6.2 kVAR

kW to kVA — Reference Table

kWPF 0.7PF 0.8PF 0.85PF 0.9PF 1.0
5 kW7.146.255.885.565
10 kW14.2912.511.7611.1110
15 kW21.4318.7517.6516.6715
20 kW28.572523.5322.2220
25 kW35.7131.2529.4127.7825
50 kW71.4362.558.8255.5650
75 kW107.1493.7588.2483.3375
100 kW142.86125117.65111.11100
150 kW214.29187.5176.47166.67150
200 kW285.71250235.29222.22200

💡 How to Convert kW to kVA

To convert kW to kVA, divide the kilowatts by the power factor. The answer is the apparent power your generator, transformer or UPS must be rated for to deliver that real power. At the generator-standard power factor of 0.8, kVA is 1.25 × kW.

kW to kVA formula

kVA = kW ÷ PF

Example: 10 kW at PF 0.85 → 10 ÷ 0.85 = 11.76 kVA

Worked examples

  • Generator for an 80 kW load (PF 0.8): 80 ÷ 0.8 = 100 kVA.
  • Transformer for a 400 kW factory at PF 0.85: 400 ÷ 0.85 = 470.6 kVA, so the next standard size up (500 kVA) is chosen.
  • UPS for 8 kW of IT equipment at PF 0.9: 8 ÷ 0.9 = 8.89 kVA.

kW to kVA table

kWkVA @ PF 0.7kVA @ PF 0.8kVA @ PF 0.85kVA @ PF 0.9kVA @ PF 1.0
11.431.251.181.111
57.146.255.885.565
811.43109.418.898
1014.2912.511.7611.1110
2028.572523.5322.2220
4057.145047.0644.4440
5071.4362.558.8255.5650
80114.2910094.1288.8980
100142.86125117.65111.11100
200285.71250235.29222.22200
400571.43500470.59444.44400

Typical power factors: resistive loads such as heaters and incandescent lamps run at 1.0; computer and server power supplies with power factor correction (PFC) run at about 0.95–0.99; induction motors run at roughly 0.8–0.9 at full load and lower when lightly loaded. Diesel generators are conventionally rated at a power factor of 0.8.

Sizing checklist

  • Total the real power (kW) of everything that runs at once.
  • Divide by the power factor to get kVA.
  • Add allowance for motor starting current, which can be several times the running current.
  • Round up to the next standard equipment size and keep roughly 20–25% headroom for growth.

Related conversions: kVA to kW · watts to kVA · kW to amps

kVA = kW ÷ power factor. An 80 kW load at PF 0.8 needs a 100 kVA generator.