kW to VA Calculator
Convert kilowatts (kW) to volt-amps (VA) using power factor: VA = kW × 1,000 ÷ PF. Size a UPS, inverter or transformer for a known real-power load.
APPARENT POWER
5,882 VA
IN kVA
5.88 kVA
FORMULA
VA = (kW×1000)/PF
POWER FACTOR
0.85
💡 How to Convert kW to VA
To convert kW to VA, multiply the kilowatts by 1,000 and divide by the power factor. Because the power factor is 1 or less, the VA figure is always equal to or larger than the watt figure. That larger number is what your UPS, inverter or transformer must be rated for.
kW to VA formula
Example: 5 kW at PF 0.85 → 5 × 1,000 ÷ 0.85 = 5,882 VA
Worked examples
- Sizing a UPS for a server rack: 0.9 kW of servers with PFC power supplies (PF 0.9) needs at least 1,000 VA. With 25% headroom, choose about 1,250 VA.
- Workshop machinery (PF 0.8): 3 kW ÷ 0.8 = 3,750 VA.
- Resistive heater (PF 1.0): 2 kW = 2,000 VA; with no reactive power, VA equals watts.
kW to VA table at common power factors
| kW | VA @ PF 0.6 | VA @ PF 0.8 | VA @ PF 0.9 | VA @ PF 1.0 |
|---|---|---|---|---|
| 0.5 | 833 | 625 | 556 | 500 |
| 0.9 | 1,500 | 1,125 | 1,000 | 900 |
| 1 | 1,667 | 1,250 | 1,111 | 1,000 |
| 1.5 | 2,500 | 1,875 | 1,667 | 1,500 |
| 2 | 3,333 | 2,500 | 2,222 | 2,000 |
| 3 | 5,000 | 3,750 | 3,333 | 3,000 |
| 5 | 8,333 | 6,250 | 5,556 | 5,000 |
| 10 | 16,667 | 12,500 | 11,111 | 10,000 |
| 20 | 33,333 | 25,000 | 22,222 | 20,000 |
| 50 | 83,333 | 62,500 | 55,556 | 50,000 |
Typical power factors: resistive loads such as heaters and incandescent lamps run at 1.0; computer and server power supplies with power factor correction (PFC) run at about 0.95–0.99; induction motors run at roughly 0.8–0.9 at full load and lower when lightly loaded. Diesel generators are conventionally rated at a power factor of 0.8.
Why a lower power factor means a bigger rating
A load with a low power factor draws more current for the same useful work. That extra current heats cables and windings even though it does no work, so equipment has to be rated for the full apparent power. Improving power factor (for example, with capacitor banks on large motor installations) reduces the VA you need.
Related conversions: VA to kW · kW to kVA · watts to kVA